INSTRUMENTATION LOGGER LR5031

4-20 mA Instrumentation Signal Logging

Hioki compact 1 or 2-channel data loggers feature a 60,000 data set/channel memory to measure temperature, humidity, voltage or instrumentation signals. The LR5031 logs instrumentation signals such as 4-20mA signals over 1 channel in as fast as 1 second intervals.

Dapatkan Penawaran

Diskusi dan Tanya Harga

Key Features

  • 4 – 20 mA DC measurement only
  • Easily mount the light-weight , pocket-sized loggers in tight spaces
  • Easy-to-see dual display
  • Transfer data to PC even during recording*
  • Replace batteries while recording (30 second limit)
  • 3 times the memory capacity than predecessor (Record 60,000 data per channel)
  • Measurement data is preserved even after the battery dies
  • Worry-free backup preserves recorded data even if a new measurement is started by mistake
  • *Optional accessory is required and sold separately.
Note: Communication Adapter LR5091 or Data Collector LR5092-20 is necessary to transfer data from a LR5000 series Logger to a PC

Basic specifications

Accuracy guaranteed: 1 year
Measurement items DC current (1 ch), for Instrumentation
Measurement range -30.00 to 30.00 mA
Accuracy ±0.5 %rdg. ±5 dgt.
Storage capacity Instantaneous value mode: 60,000 data, Statistical value mode: 15,000 data
Recording interval 1 to 30 sec., 1 to 60 min., 15 selections
Recording modes Instantaneous recording: at every recording interval
Statistical value recording: Measure at one second intervals, and record the instantaneous, maximum, minimum, and average values within every recording interval
Recording methods One-time recording: Stop recording when the memory capacity is full
Endless recording: Continue recording even when the memory capacity is full (old data is overwritten)
Start: Logger button operation or scheduled time
Stop: Logger button operation or scheduled time, or auto-stop when the memory capacity is full (at one-time recording)
Other functions Always backs up last recorded data; backs up recorded data and setting conditions when battery power is low; guarantees approx. 30 sec. of recording operation and clock while battery is replaced
Waterproof and dust-proof IP54 (EN60529) (with connection cable connected, but not including cable tip)
Interfaces Infrared optical communications with LR5091, LR5092-20
Power supply LR6 (AA) Alkaline battery ×1, Battery life: Approx. 2 years (Instantaneous recording, with 1-minute interval and auto power saving, at 20 °C), Approx. 2 months (Instantaneous recording, with 1-second interval at 20 °C)
Dimensions and mass 79 mm (3.11 in) W × 57 mm (2.246 in) H × 28 mm (1.10 in) D, 105 g (3.7 oz)
Included accessories LR6 (AA) Alkaline battery (built-in internal) ×1, Connection Cable LR9801 ×1, Instruction manual ×1, Operation guide ×1, Kickstand ×1

Kami adalah perusahaan yang bergerak di bidang industrial supply company, berdiri sejak tahun 2010. 

Menyediakan berbagai kebutuhan industri dan bisnis, mulai dari produk MRO (Maintenance, Repair, and Operation), alat keselamatan, perkakas tangan dan elektrik, alat kebersihan, hingga alat ukur dan analisa listrik

Cilegon Office & KARCHER Service Center:
Jl Boulevard Raya no 36-38. Ruko Grand Cilegon Resident Cibeber. Cilegon-Banten, Indonesia 4242
Phone / fax  : 0254 375765 / 0254 387163

Surabaya Office:
Jl. Puri Kencana Karah B-5 Surabaya 60232
Phone : 031 825 31779 

Chat Kami